Uploaded image for project: 'PROFINET IO-Device V4'
  1. PROFINET IO-Device V4
  2. PSPNSV4-487

ReadImplicit of object ExpectedIdentificationData (index 0x8000) with invalid TargetARUUID is not rejected

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V4.2.0.0
    • Fix Version/s: V4.2.1.0
    • Labels:
      None
    • Sprint:
      PI Sprint 2016 KW 47/48
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      A ReadImplicit for object ExpectedIdentificationData (index 0x8000) is accepted if the TargetARUUID inside the request is NIL.
      According to Profinet specification ExpectedIdentificationData needs an ARUUID context. Thus in this case the request shall be rejected (as PNSv3 does).

        Attachments