Uploaded image for project: 'PROFINET IO-Device V4'
  1. PROFINET IO-Device V4
  2. PSPNSV4-458

Inconsistency between GSDML and Stack for supported DCP ResetToFactory Modes (certification issue)

    Details

    • Sprint:
      PI Sprint 2016 KW 18/19
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      According to actual GSDML "GSDML-V2.32-HILSCHER-NETX 51-RE PNS-20160302" DAP "NETX 51 RE/PNS V4.2.0.x" only reset to factory mode 2 (Reset communication parameter) is supported but the Stack does not reject DCP reset to factory request with following modes :
      1 : Reset application data (optional)
      3 : Reset engineering parameter (optional)
      8 : Reset device - out of the box state (optional)

        Attachments

          Issue Links

            Expenses

              Activity

                Status Description

                  People

                  • Reporter:
                    RAamidi Redouane Aamidi
                  • Votes:
                    0 Vote for this issue
                    Watchers:
                    0 Start watching this issue

                    Dates

                    • Created:
                      Updated:
                      Resolved: