Details
-
Type: Bug
-
Status: Closed
-
Priority: Minor
-
Resolution: Fixed
-
Affects Version/s: None
-
Fix Version/s: V4.2.1.0
-
Labels:None
-
Sprint:PI Sprint 2016 KW 36, PI Sprint 2016 KW 50/51
-
Account:SPC Profinet Slave (SPCPROFINE)
Description
If the IP of the integrated LWIP task is changed via Hilscher specific netIdent protocol the Profinet protocol stack does not detect this IP change. Thus as a result acyclic Profinet communication is no longer possible.
In this situation the Profinet protocol stack reports the wrong, old IP address via DCP and thus a new cyclic communication can not be established.
Expected reaction is that the Profinet protocol stack detects this situation and delivers the real IP via DCP.
Attachments
Issue Links
- clones
-
PSPNS-2425 in case IP is changed via netIdent the reaction of the protocol stack is not sufficient
- Closed