Uploaded image for project: 'PROFINET IO-Device V4'
  1. PROFINET IO-Device V4
  2. PSPNSV4-429

Invalid process data when using more than one API

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Major
    • Resolution: Fixed
    • Affects Version/s: V4.0.0.0, V4.1.0.0, V4.2.0.0
    • Fix Version/s: V4.1.0.3, V4.2.0.2, V4.2.1.0
    • Labels:
      None
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      When the application configures multiple APIs input process data might not be send to the Controller and output process data might not be received at the application. Only the submodules belonging to the last API described in the corresponding IOCR block are handled as expected.

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  AMesser Andreas Messer
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: