Details
-
Type: Bug
-
Status: Closed
-
Priority: Minor
-
Resolution: Fixed
-
Affects Version/s: V4.4.0.0
-
Labels:
-
Account:SPC Profinet Slave (SPCPROFINE)
Description
A data inconsistency issue exists if
- the neighbor device connected on a port is supporting LLDP protocol but is not a Profinet device
- the neighbor LLDP frame uses ChassisID subtype 7 (locally assigned) in its LLDP frame
The issue itself is an inconsistency between
- PDPortDataReal.PeerStationName (if accessed via Record Read) and
- lldpXPnoRemPortNoS (if accessed via SNM)
It is expected that both access ways deliver the same content. However, if conditions mentioned above are met, the data is different.
This happens if e.g. a cisco switch is used as neighbor. In this case PeerStationName is the ChassisID of cisco Switch but lldpXPnoRemPortNoS contains the MAC Address of the switch.
Attachments
Issue Links
- clones
-
PSPNSV5-255 inconsistent NameOfStation reported in different access ways in case of Non-Profinet neighbor
- Closed
- is blocked by
-
PSPNSV4-1187 Upgrade Profinet Core to V1.9.0.12
- Closed