Details
Description
When the application does not register with the firmware or the application relies on PNS_IF_IO_EVENT_PROVIDER_UPDATE_REQUIRED only, the firmware might not signal application ready to the controller. The connection is not fully established.
In these situations, it is expected that the application ready is sent.
Workaround: Do not rely on IO events but periodically exchange the DPM Output Area.
Attachments
Issue Links
- blocks
-
PSPNCORE-397 Provider Update Required event generated before work lists updated
- Closed
-
PSPNSV4-1178 Upgrade Profinet Core to V1.9.0.11
- Closed
- discovered by
-
PSPNSV5-227 Application Ready sometimes not send
- Closed