Uploaded image for project: 'PROFINET IO-Device V4'
  1. PROFINET IO-Device V4
  2. PSPNSV4-1166

AR state Indications sometimes not generated

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V4.4.2.0
    • Fix Version/s: V4.5.0.3, V4.5.1.0, V4.6.0.0
    • Labels:
      None
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      When an AR state changes during a pending Read or Write Record Service, the AR state change might not been reported to the application immediately. Reporting the AR state change is delayed until another AR State Change occurs. This leads to a possibly infinite long delay of the following services:

      • AR Indata Indication service
      • AR Abort Indication service

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  AMesser Andreas Messer
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: