Details
-
Type: Bug
-
Status: Closed
-
Priority: Minor
-
Resolution: Fixed
-
Affects Version/s: V3.6.4.0
-
Fix Version/s: V3.6.6.0
-
Labels:None
-
Sprint:PI Sprint KW 31/32 2014
-
Account:SPC Profinet Slave (SPCPROFINE)
Description
using configuration database with "application controlled" startup the firmware does not activate the Ethernet ports. So no link can be established and no switching in a line is possible.
When using NRP52 this leads to the following effect:
both Ethernet Link LEDs are static on but no link is established (LED is on even if no cable plugged).