Uploaded image for project: 'PROFINET IO-Device'
  1. PROFINET IO-Device
  2. PSPNS-2929

AR aborted unexpectedly when several ARs are being established simultaneously.

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.13.0.0, V3.14.0.0
    • Fix Version/s: V3.14.0.8, V3.14.1.0
    • Component/s: Stack
    • Labels:
      None

      Description

      In case Shared Device, when several ARs are establshing in parallel, the first AR may be aborted with error "CMI Timeout".

      This issue occurs only when the second AR is being established while the first one is not yet completely established but CPM is already started (CMDEV State between "PrmEnd" and "Data").
       

        Attachments

          Issue Links

            Expenses

              Activity

                Status Description

                  People

                  • Reporter:
                    RAamidi Redouane Aamidi
                  • Votes:
                    0 Vote for this issue
                    Watchers:
                    0 Start watching this issue

                    Dates

                    • Created:
                      Updated:
                      Resolved: