Uploaded image for project: 'PROFINET IO-Device'
  1. PROFINET IO-Device
  2. PSPNS-2903

Unexpected IOCS reported in acyclic object to read Cyclic data if read via DeviceAccess AR

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.14.0.0
    • Fix Version/s: V3.14.0.13, V3.14.1.0
    • Component/s: None
    • Labels:
      None

      Description

      When the acyclic object to read the cyclic data (index 0x8028, RecordInputDataObjectElement) is read via DeviceAccess AR, an IOCS "good" is returned which is valid according to specification.

      However, the recommendation is using a different value "bad" here. The Automated certification tool shows a hint regarding this topic.

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  BMeyer Benjamin Meyer
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: