Uploaded image for project: 'PROFINET IO-Device'
  1. PROFINET IO-Device
  2. PSPNS-2875

In case of wrong usage of fix port configuration in engineering and IRT is used firmware may run in fatal error

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.13.0.0
    • Fix Version/s: V3.13.0.6, V3.13.4.0, V3.14.0.0
    • Component/s: None
    • Labels:
      None
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      The Profinet IO Device protocol stack may unexpectedly enter fatal error state with error code 0xC00B001F  (TLR_E_PNIO_CMDEV_EMPTY_POOL_DETECTED) in the following scenario:

      • IO Device is directly connected to IO Controller
      • IRT is active
      • IO Controller port is configured to "Autonegotiation"
      • IO Device port is configured to "100MBit/s FullDuplex"

      The error only occurs if IRT is used. In RT mode the same situation does not lead to fatal error.

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  BMeyer Benjamin Meyer
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: