Uploaded image for project: 'PROFINET IO-Device'
  1. PROFINET IO-Device
  2. PSPNS-2845

wrong FSHelloMode reported in case Controller uses strange FSU parameters

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.12.0.0
    • Fix Version/s: V3.13.0.3, V3.13.2.0, V3.14.0.0
    • Component/s: None
    • Labels:
      None
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      If the device supports FSU using the certification testcase FSU of new testtool ART 2.33.3 shows an error.

      The testcase uses mode "Issue Hello with additional delay after LinkUp" but sets the additional delay to 0. The current implementation will incorrectly store the mode "Issue Hello after LinkUp" in this case which is technical identical but still wrong.

        Attachments

          Issue Links

            Expenses

              Activity

                Status Description

                  People

                  • Reporter:
                    BMeyer Benjamin Meyer
                  • Votes:
                    0 Vote for this issue
                    Watchers:
                    0 Start watching this issue

                    Dates

                    • Created:
                      Updated:
                      Resolved: