in case application reports the same PE OperationMode twice the PE-ASE issues an unexpected update alarm

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Trivial
    • Resolution: Fixed
    • Affects Version/s: V3.12.0.0
    • Fix Version/s: V3.13.0.1, V3.13.2.0, V3.14.0.0
    • Component/s: None
    • Labels:
      None
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      When using Profienergy service PNS_IF_UPDATE_PE_ENTITY_REQ with the same OperationMode multiple times current implementation of PE ASE in protocol stack will issue an Update alarm every time the service is used.

      After clarification with Siemens Profienergy experts no Update alarm shall be generated when the same OperationMode does not change.
       