Uploaded image for project: 'PROFINET IO-Device'
  1. PROFINET IO-Device
  2. PSPNS-2693

in case a SetConfig packet from AP task based on database is rejected by protocol stack the AP task does not set Ready bit

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.12.0.0
    • Fix Version/s: V3.12.0.10, V3.12.2.0, V3.13.0.0
    • Component/s: None
    • Labels:
      None
    • Sprint:
      PI Sprint 2018 KW 5
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      If a database is evaluated wrongly by AP task (leading to an invalid SetConfig packet) and a ChannelInit is requested via driver functions the CommunicationChannel will never get Ready any more. Thus it is impossible to exchange any packet with the AP task.