Uploaded image for project: 'PROFINET IO-Device'
  1. PROFINET IO-Device
  2. PSPNS-2468

4th Ethernet Mac Address configured to switch, leading to unexpectedly not forwarded frames of specific other device

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Major
    • Resolution: Fixed
    • Affects Version/s: V3.4.144.0
    • Fix Version/s: V3.4.148.2
    • Component/s: None
    • Labels:
      None
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      The feature of the PROFINET IO Device switch to use a 4th Ethernet Mac Address is unexpectedly actived in the switch. As a result, the Switch will by default drop any frame with the Mac-Address "1st (Device) Ethernet Mac Address +3". By default the 4th Mac Address shall not be active in the switch.

      This issue only affects PNS V3.4.1xx.x versions.
      PNS V3.4.xx.x (thus third number below 100) is not affected by this issue.