Uploaded image for project: 'PROFINET IO-Device'
  1. PROFINET IO-Device
  2. PSPNS-2416

cyclic data consistency with asynchronous host not guaranteed on IRT communication

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.5.33.0
    • Fix Version/s: V3.9.3.0, V3.10.0.0
    • Component/s: Stack
    • Labels:
      None
    • Sprint:
      PI Sprint 2016 KW 10/11
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      This issue can be reproduced only in IRT mode with an asynchronous application that writes its data in provider image (in case of DPM it is the output data area) asynchronously relative to the IRT bus cycle. It sometimes happens that the data transfered on the network is a mix of data from the previos host data and the current host data. The next cyclic frame will have consistent data.

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  Artem Artem R. [X] (Inactive)
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: