Uploaded image for project: 'PROFINET IO-Device'
  1. PROFINET IO-Device
  2. PSPNS-2325

reject PDPortDataAdjust if both ports are adjusted to "LinkDown"

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.8.0.0
    • Fix Version/s: V3.9.0.1, V3.9.1.0, V3.10.0.0
    • Component/s: None
    • Labels:
      None
    • Sprint:
      PI Sprint KW 40/41 2015
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      If an IO.Controller sends PDPortDataAdjust and one of the following situations exist the record shall be rejected with "invalid parameter":

      • for 2 port IO Device both ports are forced to "LinkDown"
      • for 1 port IO Device the only port is forced to "LinkDown"