Uploaded image for project: 'PROFINET IO-Device'
  1. PROFINET IO-Device
  2. PSPNS-2269

[cifX]: when using DMA and length of data sent to IO Controller is 0 no connection to IO Controller can be established

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Major
    • Resolution: Fixed
    • Affects Version/s: V3.5.53.0
    • Fix Version/s: V3.5.52.1, V3.8.2.0, V3.9.0.0
    • Component/s: None
    • Labels:
      None
    • Sprint:
      PI Sprint KW 25/26 2015
    • Account:
      SPC Profinet Slave (SPCPROFINE)
    • Story Points:
      1

      Description

      cifX allows usage of DMA feature.
      If this is active and the length of IO Data to be transfered to IO Controller is 0 than no ApplicationReady is sent on the bus, even if it is manually triggered by application.

      The same application works fine without DMA. In that case ApplicationReady is sent.

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  BMeyer Benjamin Meyer
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: