Uploaded image for project: 'PROFINET IO-Device'
  1. PROFINET IO-Device
  2. PSPNS-2208

Wrong Responses when Reading Record Data Objects

    Details

    • Account:
      SPC Profinet Slave V5 operational (SPCPROFINE)

      Description

      The new upcoming PI certification tool Profinet IO Tester V2.32 revealed several errors in Read Handling of Record Data Objects. The following issues are discovered:

      • IOC/DA/IMP Read 0xF842: Is not empty
      • DA Read 0xF020: Is not empty
      • IOC Read 0xE050: Should Fail for Advanced Startup AR
      • DA/IMP Read 0xE050: Should Fail.
      • IOC/DA/IMP Read 0x801E: Is rejected
      • IOC/DA/IMP Read 0x8071: Is not empty
      • IOC/DA/IMP Read 0x8080: Wrong content

      Despite these Stack issues, the NX LOM Example does not reject several Reads: 0x80A0- 0x80AF, 0x8030 ( used non-isochrone gsdml)

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  AMesser Andreas Messer
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: