Uploaded image for project: 'PROFINET IO-Device'
  1. PROFINET IO-Device
  2. PSPNS-2208

Wrong Responses when Reading Record Data Objects

    Details

    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      The new upcoming PI certification tool Profinet IO Tester V2.32 revealed several errors in Read Handling of Record Data Objects. The following issues are discovered:

      • IOC/DA/IMP Read 0xF842: Is not empty
      • DA Read 0xF020: Is not empty
      • IOC Read 0xE050: Should Fail for Advanced Startup AR
      • DA/IMP Read 0xE050: Should Fail.
      • IOC/DA/IMP Read 0x801E: Is rejected
      • IOC/DA/IMP Read 0x8071: Is not empty
      • IOC/DA/IMP Read 0x8080: Wrong content

      Despite these Stack issues, the NX LOM Example does not reject several Reads: 0x80A0- 0x80AF, 0x8030 ( used non-isochrone gsdml)