MRP is active even if it was disabled by Profinet IO Controller

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Major
    • Resolution: Fixed
    • Affects Version/s: V3.5.26.0
    • Fix Version/s: V3.5.33.0
    • Component/s: None
    • Labels:
      None
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      MRP functionality is always enabled even if it's deactivated explicitly in the configuration. This means that only one Port is active and that Multicast frames are sent only on the active port (Primary). this is critical if FSU is enabled.