Uploaded image for project: 'PROFINET IO-Device'
  1. PROFINET IO-Device
  2. PSPNS-1608

sometimes SharedDevice not working as expected (connection not established and existing one is aborted)

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Major
    • Resolution: Fixed
    • Affects Version/s: V3.5.28.0
    • Fix Version/s: V3.5.29.0
    • Component/s: Stack
    • Labels:
      None
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      In some situations when SharedDevice is used no stable connection can be established. After the first connection is established and when the second one is in establishment phase both are shut down by the protocol stack. This depends on the coding of the IO-Controllers ConnectRequest (can easily be triggered with CPU319F FW 3.2.8)

        Attachments

          Issue Links

            Expenses

              Activity

                Status Description

                  People

                  • Reporter:
                    BMeyer Benjamin Meyer
                  • Votes:
                    0 Vote for this issue
                    Watchers:
                    0 Start watching this issue

                    Dates

                    • Created:
                      Updated:
                      Resolved: