Uploaded image for project: 'PROFINET IO-Device'
  1. PROFINET IO-Device
  2. PSPNS-1385

SystemReset does not work if IRT communication is active (firmware is unresponsible)

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.4.39.0
    • Fix Version/s: V3.4.40.0
    • Component/s: Stack
    • Labels:
      None
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      If pns device runs in IRT mode, an application receives CIFX_DEV_NOT_READY (0x800c0011 - Device not ready (ready flag failed)) error on reset request

      python function: iod.channel.Reset(CIFX_SYSTEMSTART)
      cifX Test Application: Device -> Reset -> Resrt, with Reset Mode: System Start