certification testcase DCPUCx is not completely handled as expected by test laboratory

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.4.39.0
    • Fix Version/s: V3.4.39.1
    • Component/s: Stack
    • Labels:
      None
    • Account:
      SPC Profinet Slave V5 operational (SPCPROFINE)

      Description

      PI testlab in USA complains:
      One nuisance failure during the PROFINET certification testing is that during the DCPUCx test of the PN test software the stack will return a resource error response from the "get station name" from MacID 00.00.00.00.00.00 while already in service prior.

      Expected behavior: there should be no response to this "get station name" request