Uploaded image for project: 'PROFINET IO-Device'
  1. PROFINET IO-Device
  2. PSPNS-1350

cifX firmware does not handle DPM Synchronization handshake.

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.4.38.0
    • Fix Version/s: V3.4.38.1
    • Component/s: Stack
    • Labels:
      None
    • Account:
      SPC Profinet Slave V5 operational (SPCPROFINE)

      Description

      In case of loadable firmawre if the IRT is active, the netX is required to indicate the Start of Bus Cycle by toggling of DPM Sync Handshake bit.
      The cifX firmware does not initialize the Sync Interrupt, which will be used to handle DPM Sync Handshake.