Details
-
Type:
Bug
-
Status: Closed
-
Priority:
Minor
-
Resolution: Fixed
-
Affects Version/s: V3.5.0.0
-
Fix Version/s: V3.6.0.3, V3.6.1.0 (trunk) (open)
-
Labels:None
-
Account:SPC Profinet Master V3 operational (SPCPROFINETMA)
Description
In case MRP Manager functionality is active, the IO Controller sends wrongly coded MRP_Test frames. The required MRP_End-TLV is missing in the frames.
Attachments
Issue Links
- relates to
-
PSPNCORE-879 invalid MRP_Test frames sent by MRP Manager (MRP_END TLV is missing)
-