Type:
Bug
-
Status: Closed
-
Priority:
Minor
-
Resolution: Fixed
-
Affects Version/s: V3.4.0.0, V3.5.0.0, V3.6.0.0
-
Fix Version/s: V3.5.0.16, V3.6.0.2 (open), V3.6.1.0 (trunk) (open)
-
Labels:None
-
Account:SPC Profinet Master V3 operational (SPCPROFINETMA)
Description
When an IO-AR is aborted after beeing in communication for about ~25 days, the controller does not immediately try to restablish this AR. The controller will consider the AR restablishing not before ~ 49 days after the previous connection has been made.
It is expected that the controller tries to re-establish the AR in a timely manner.
Attachments
Issue Links
- is blocked by
-
PSPNCORE-868 Long delay in AR Connect sequencing of Controller
-
- Closed
-
- requested
-
PSPNMV3-963 Upgrade Profinet Core to V1.16.0.3
-
- Resolved
-
-
PSPNMV3-962 Upgrade Profinet Core to V1.14.0.15
-
- Closed
-