Details
-
Type:
Bug
-
Status: Closed
-
Priority:
Minor
-
Resolution: Fixed
-
Affects Version/s: None
-
Fix Version/s: V3.5.0.14, V3.6.0.1, V3.6.1.0 (trunk) (open)
-
Labels:None
-
Account:SPC Profinet Master V3 operational (SPCPROFINETMA)
Description
The stack provides the possibility to control the status of the individual ARs using PNM_AP_CMD_CHANGE_ARSTATE_REQ.
For example, the application can switch off the individual ARs at runtime using the ‘PNM_AP_ARSTATE_REQ_SHUTDOWN’ status. However, if the bus status is then switched to ON, either explicitly through the DPM service or implicitly through the status ‘PNM_AP_ARSTATE_REQ_SHUTDOWN’ for handle 0 (IO controller), all ARs are established, including those previously deactivated.
Attachments
Issue Links
- requested
-
PSPNMV3-947 Update Profinet Controller Interface to V1.1.0.10
-
- Closed
-
-
PSPNMV3-951 Upgrade Profinet Controller Interface to V1.2.0.1
-
- Closed
-