When the controller stack is switched to bus off and back to bus on, the firmware may send old or wrong process data to devices after re-establishing the connection. The problem might occur whenever the controller starts establishing connections after:
- Configure or reconfigure controller while using application controlled startup (This includes ChannelInit to load database)
- Switch bus state to bus on via packet or DPM
The problem might be hidden, if application manages to write DPM Output area at least three times before a connection is established.
Attachments
Issue Links
- relates to
-
PSPNMV3-341 invalid (old) IO Data sent to network after configuration is changed
- Closed
- requested
-
PSPNCORE-562 Old or wrong process data send to devices after repeated switch to Bus On
- Closed
-
PSPNMV3-737 Upgrade Profinet Core to V1.12.0.7
- Closed