Old or wrong process data send to devices after repeated switch to Bus On

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Major
    • Resolution: Fixed
    • Affects Version/s: V3.1.2.0, V3.2.0.0, V3.3.0.0, V3.4.0.0
    • Fix Version/s: V3.4.0.9, V3.4.4.0
    • Labels:
      None
    • Account:
      SPC Profinet Master (SPCPROFINETMA)

      Description

      When the controller stack is switched to bus off and back to bus on, the firmware may send old or wrong process data to devices after re-establishing the connection. The problem might occur whenever the controller starts establishing connections after:

      • Configure or reconfigure controller while using application controlled startup (This includes ChannelInit to load database)
      • Switch bus state to bus on via packet or DPM

      The problem might be hidden, if application manages to write DPM Output area at least three times before a connection is established.