Uploaded image for project: 'PROFINET IO-Controller V3'
  1. PROFINET IO-Controller V3
  2. PSPNMV3-563

Unexpected loss of cyclic communication to IO Devices connected to Ethernet port 2

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.3.0.0
    • Fix Version/s: V3.3.0.9, V3.3.1.0
    • Labels:
      None
    • Account:
      SPC Profinet Master (SPCPROFINETMA)

      Description

      Under some circumstances the connection to Profinet IO Devices may unexpectedly be interrupted by IO Controller with error code "CPM DHT/Watchdog failure" although the IO Device has sent all expected cyclic frames.

      The exact details of the issue and its reproducability are not 100% clear but only Ethernet port 2 seems to be affected by current knowledge.

      This issue is independend of the existing network load or parallel traffic in network. It is already observed when only 2 IO Devices are connected to IO Controller.

      Additing additional acyclic traffic (e.g. cyclic ReadRecord requests) may increase probability of the issue but even that is not 100% confirmed.

        Attachments

          Issue Links

            Expenses

              Activity

                Status Description

                  People

                  • Reporter:
                    BMeyer Benjamin Meyer
                  • Votes:
                    0 Vote for this issue
                    Watchers:
                    0 Start watching this issue

                    Dates

                    • Created:
                      Updated:
                      Resolved: