Uploaded image for project: 'PROFINET IO-Controller V3'
  1. PROFINET IO-Controller V3
  2. PSPNMV3-430

RCX_UNREGISTER_APP_REQ is not accepted by firmware in some cases (e.g. using TCP Server)

    Details

    • Type: Change
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.2.0.0
    • Fix Version/s: V3.2.0.2, V3.3.0.0
    • Labels:
      None
    • Account:
      SPC Profinet Master (SPCPROFINETMA)

      Description

      It is expected that the firmware always accepts the generic request RCX_UNREGISTER_APP_REQ, independend from the sender of the request.

      Current firmware implementation only accepts this request if the sender is exactly the same. If the sender is different (which may happen using TCP Server by simply reconnecting the same application to firmware) the firmware rejects the request with error 0xC0000002.

      Same error would occur if application via DPM would change the value of field ulSrcID in request packet.

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  BMeyer Benjamin Meyer
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: