Sending DCP Factory Reset using old encoding not possible

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.2.0.0
    • Fix Version/s: V3.2.0.1, V3.3.0.0
    • Labels:
      None
    • Account:
      SPC Profinet Master (SPCPROFINETMA)

      Description

      When host application requests a DCP Reset To Factory service using the old Profinet Encoding (Blockqualifier == 0) the firmware rejects the service with error code 0xC0000009 (RCX_E_INVALID_PARAMETER). It is expected that this service is not rejected.