Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.1.1.0
    • Fix Version/s: V3.1.2.0, V3.2.0.0
    • Labels:
      None
    • Account:
      SPC Profinet Master (SPCPROFINETMA)

      Description

      If the configuration contains an IO Device that is unreachyble by means of IP (because it is using a different subnet) the whole configuration shall be rejected as "invalid".

      Current implementation accepts such configuration, performs DCP recovery, sets the unreachable IP and gets stuck