Uploaded image for project: 'PROFINET IO-Controller V3'
  1. PROFINET IO-Controller V3
  2. PSPNMV3-340

in case no port offers 100MBit/s FullDuplex no AR shall be established

    Details

    • Type: Change
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: None
    • Fix Version/s: V3.1.2.0, V3.2.0.0
    • Labels:
      None
    • Account:
      SPC Profinet Master (SPCPROFINETMA)

      Description

      If no Ethernet port of IO Controller offers 100MBit/s FullDuplex the IO Controller shall not establish any AR.
      Instead it shall abort the AR with error code 0xCF81FD24 "no port offers required Speed or duplexity" after receipt of ApplicationReady.