Uploaded image for project: 'PROFINET IO-Controller V3'
  1. PROFINET IO-Controller V3
  2. PSPNMV3-328

Session monitoring not activated for Legacy Startup Mode

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.1.0.0
    • Fix Version/s: V3.1.2.0, V3.2.0.0, V3.3.0.0
    • Labels:
      None
    • Account:
      SPC Profinet Master (SPCPROFINETMA)

      Description

      When legacy startup mode is used, the connection monitoring is activated when the first cyclic frame is received from the device after application ready. Thus between Connect and Application Ready no session monitoring is done. According to specification V2.2 session monitoring is done by means of connection monitoring which is activated after receiving the connect response.