Details
-
Type: Bug
-
Status: Closed
-
Priority: Minor
-
Resolution: Fixed
-
Affects Version/s: V2.7.0.0
-
Fix Version/s: V2.7.1.0
-
Component/s: None
-
Labels:None
-
Account:SPC Profinet Master (SPCPROFINETMA)
Description
If an IO Device sends a Plug (or Release) alarm directly after its ApplicationReady Request, which is the last step of connection establishment, and if the network cycle time of this IO Device is slow it may happen that IO Controller does not correctly handle the alarm.
In case of error IO Controller will not send Parameters to IO Device and instead directly confirm the alarm.
Attachments
Issue Links
- relates to
-
PSPNS-2511 In case of ownership change directly after a new AR is established it may happen that IO Device rejects the submodule parameterization and aborts the AR
- Closed