Uploaded image for project: 'PROFINET IO-Controller'
  1. PROFINET IO-Controller
  2. PSPNM-701

Plug and Release alarms may not be handled correctly in case of slow bus cycle time and alarm directly after connection establishment

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V2.7.0.0
    • Fix Version/s: V2.7.1.0
    • Component/s: None
    • Labels:
      None
    • Account:
      SPC Profinet Master (SPCPROFINETMA)

      Description

      If an IO Device sends a Plug (or Release) alarm directly after its ApplicationReady Request, which is the last step of connection establishment, and if the network cycle time of this IO Device is slow it may happen that IO Controller does not correctly handle the alarm.

      In case of error IO Controller will not send Parameters to IO Device and instead directly confirm the alarm.

        Attachments

          Issue Links

            Expenses

              Activity

                Status Description

                  People

                  • Reporter:
                    BMeyer Benjamin Meyer
                  • Votes:
                    0 Vote for this issue
                    Watchers:
                    0 Start watching this issue

                    Dates

                    • Created:
                      Updated:
                      Resolved: