Uploaded image for project: 'PROFINET IO-Controller'
  1. PROFINET IO-Controller
  2. PSPNM-699

an IO Device reporting ModuleDiffBlock with only Diagnosis is reported as faulty even if all diagnosis is gone

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V2.7.0.0
    • Fix Version/s: V2.7.0.9, V2.7.1.0
    • Component/s: None
    • Labels:
      None
    • Account:
      SPC Profinet Master (SPCPROFINETMA)

      Description

      In case an IO Device reports a ModuleDiffBlock at ConnectionEstablishment which only states that diagnosis exists, thus all expected modules are present, and later this IO Device reports all diagnosis is gone it is still reported as faulty by IO Controller firmware to its application.
      The ModuleDiffBlock is still reported to exist.

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  BMeyer Benjamin Meyer
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: