Uploaded image for project: 'PROFINET IO-Controller'
  1. PROFINET IO-Controller
  2. PSPNM-474

No separate configuration of PHY settings for ports 0 and 1 possible

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V2.6.9.1
    • Fix Version/s: V2.6.10.0
    • Component/s: Firmware
    • Labels:
      None
    • Account:
      SPC Profinet Master (SPCPROFINETMA)

      Description

      Configure ethernet ports 0 and 1 with different settings (MAU type AUTO and 100 MBit/s Full Duplex).

      In SYCON.net PNM DTM:
      "Controller Settings" -> "Port Settings"

      Or packet configuration:
      PNM_APCTL_CMD_SET_CONFIG_PNM_EXT_REQ parameters usMAUTypePort0 and usMAUTypePort1.

      Port 1 configuration is never used.
      Port 0 and 1 will have the same setting as configured for port 0.

      Can be checked by connecting to a PNIO device with 100 MBit/s Full Duplex setting on both ports.
      When both connected ports of two devices are 100 MBit/s Full Duplex, link is only possible between port 0 on one device and port 1 on the other (using a patch cable).

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  BMeyer Benjamin Meyer
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: