Details
- 
    Type:Bug 
- 
    Status: Closed
- 
    Priority:Minor 
- 
    Resolution: Won't Fix
- 
    Affects Version/s: V2.6.7.0
- 
    Fix Version/s: None
- 
    Component/s: Firmware
- 
    Labels:None
- 
        Account:SPC Profinet Master V3 operational (SPCPROFINETMA)
Description
if several IO-Devices are configured and none is connected an error is reported by the firmware. If now a single of the configured IO-Devices is connected and the communication is established firmware clears communication error and error flag bit. One second later it sets communication error TLR_E_CONNECTION_TIMEOUT (0xC0000142) again, since not all slaves are connected yet.
I would expect communication error to stay set, until all slaves are connected.