Details
-
Type: Bug
-
Status: Closed
-
Priority: Minor
-
Resolution: Won't Fix
-
Affects Version/s: V2.6.7.0
-
Fix Version/s: None
-
Component/s: Firmware
-
Labels:None
-
Account:SPC Profinet Master (SPCPROFINETMA)
Description
if several IO-Devices are configured and none is connected an error is reported by the firmware. If now a single of the configured IO-Devices is connected and the communication is established firmware clears communication error and error flag bit. One second later it sets communication error TLR_E_CONNECTION_TIMEOUT (0xC0000142) again, since not all slaves are connected yet.
I would expect communication error to stay set, until all slaves are connected.