  2. PSPNM-452

directly after connection establishment IOPS good is transfered to IO-Device even if user manually sets IOPS to bad in DPM

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V2.6.6.0
    • Fix Version/s: V2.6.7.0
    • Component/s: Firmware
    • Labels:
      None
    • Account:
      SPC Profinet Master (SPCPROFINETMA)

      Description

      if user sets configures stack that user sets IOPS the IO-Controller still initializes IOPS to "good" after connection establishment, even if user never wrote a good IOPS to DPM

        Attachments

          Issue Links

            Expenses

              Activity

                Status Description

                  People

                  • Reporter:
                    BMeyer Benjamin Meyer
                  • Votes:
                    0 Vote for this issue
                    Watchers:
                    0 Start watching this issue

                    Dates

                    • Created:
                      Updated:
                      Resolved: