Uploaded image for project: 'PROFINET IO-Controller'
  1. PROFINET IO-Controller
  2. PSPNM-445

packet configuration with duplicate ARUUID is accepted but should not

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V2.6.6.0
    • Fix Version/s: V2.6.7.0
    • Component/s: Firmware
    • Labels:
      None
    • Account:
      SPC Profinet Master (SPCPROFINETMA)

      Description

      if the packet configuration contains multiple IO-Devices and they use the same ARUUID this is a configuration fault. However the firmware does not detect this fault and uses the faulty configuration leading to strange behavior (e.g. ApplReady not accepted, communication not established)

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  BMeyer Benjamin Meyer
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: