[netX90/netX4000] sometimes RUN Flag not set as expected

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V0.0.0.0
    • Fix Version/s: V1.0.0.0
    • Component/s: None
    • Labels:
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      If firmware is configured with database (or with packet) and the following sequence is executed the RUN flag is not set in DPM although expected.

      • start cyclic communication with IO Controller
      • disconnect controller to stop cyclic communication
      • Perform Channel Init 2 times

      Observed behavior: RUN flag in Device COS Flags is not set, until cyclic communication with controller starts.

      Expected behavior: RUN flag to be set, when device is configured.