Details
-
Type:
Bug
-
Status: Closed
-
Priority:
Minor
-
Resolution: Fixed
-
Affects Version/s: V0.0.0.0
-
Fix Version/s: V1.0.0.0
-
Component/s: None
-
Labels:
-
Account:SPC Profinet Slave V5 operational (SPCPROFINE)
Description
If firmware is configured with SetConfigurationRequest via mailbox and Automatic startup is set and now HIL_GET_COMMON_STATE_REQ is sent to firmware the corresponding confirmation may report "Bus OFF". Expected is "Bus ON".