Details
-
Type:
Bug
-
Status: Closed
-
Priority:
Minor
-
Resolution: Fixed
-
Affects Version/s: V1.16.1.0
-
Fix Version/s: V1.16.0.9, V1.17.0.3 (open), V1.17.2.0 (trunk)
-
Component/s: Controller
-
Labels:None
-
Account:SPC Profinet Core V1 operational (SPCPROFINET)
Description
When the controller writes the PDInterfaceMRPDataCheck record using Version 1.1, a wrong coding is used. The PDInterfaceMRPDataCheck V1.1 block is missing but the record immediately starts with MrpInstanceDataCheck subblock.
Attachments
Issue Links
- blocks
-
PSPNMV3-984 Invalid PDInterfaceMRPDataCheck V1.1 coding when writing PDInterfaceMRPDataCheck record
-
- Closed
-
-
PSPNMV3-981
Upgrade Profinet Core to V1.16.0.10
-
- Closed
-