Details
-
Type:
Bug
-
Status: Closed
-
Priority:
Minor
-
Resolution: Fixed
-
Affects Version/s: V1.15.0.0
-
Fix Version/s: V1.15.0.12, V1.16.0.6, V1.16.4.0, V1.17.1.x (trunk)
-
Component/s: None
-
Labels:None
-
Account:SPC Profinet Core V1 operational (SPCPROFINET)
Description
In IRT operation mode when SyncFrames use FollowUp (e.g. because ERTEC400 based device like Scalance X204IRT is in the network), the Delay1ns field of the FollowUp Frame is wrongly used when calculating the SyncMaster time.
Attachments
Issue Links
- discovered by
-
PSPNSV4-1656 sometimes IRT communication not possible when directly connected to ERTEC4000 based Scalance switch
-
- Closed
-
-
PSPNSV5-837 sometimes IRT communication not possible when directly connected to ERTEC4000 based Scalance switch
-
- Closed
-
- relates to
-
PSPNSV4-1655
update Profinet Core to V1.15.0.12
-
- Closed
-
-
PSPNSV5-839
update Profinet Core to V1.16.0.6
-
- Closed
-
-
PSPNSV5-840
update Profinet Core to V1.15.0.12
-
- Closed
-