Uploaded image for project: 'PROFINET Core'
  1. PROFINET Core
  2. PSPNCORE-450

Wrong values reported in lldpXPnoConfig mib table

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V1.2.0.0
    • Fix Version/s: V1.12.3.0
    • Component/s: None
    • Labels:
    • Account:
      SPC Profinet Core (SPCPROFINET)

      Description

      Currently reading the MIB objects lldpXPnoConfigMrpTxEnable and

      lldpXPnoConfigPtcpTxEnable always returns "false". (hard-coded). However, since in case of enabled PTCP Sync and/or MRP the firmware sends the related LLDP TLVs, it is wrong the report false.
       
      It is expected, that the objects return the proper values depending on wheter or not the firmware is sending the associated LLDP TLVs.

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  AMesser Andreas Messer
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: