Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V1.1.2.0
    • Fix Version/s: V1.1.3.0
    • Component/s: None
    • Labels:
      None
    • Sprint:
      PI Sprint KW 16 2015
    • Account:
      SPC Profinet Core (SPCPROFINET)

      Description

      when FactoryReset request is performed using ethenet device configuration tool the stack reports a wrong usResetCode value (0xF), which is not defined to the application.

      enum PNIO_DCP_SUBOPTION_RESET_OUT_OF_THE_BOX in PNIO_DCP_SUBOPTION_RESET_E should be set to 0x10.

        Attachments

          Issue Links

            Expenses

              Activity

                Status Description

                  People

                  • Reporter:
                    RAamidi Redouane Aamidi
                  • Votes:
                    0 Vote for this issue
                    Watchers:
                    0 Start watching this issue

                    Dates

                    • Created:
                      Updated:
                      Resolved: