Details
Description
When Generic AP is configured for Free Run I/O Mode, the error detection implementation in Profinet might detect a violation of the allowed update interval and stop communication.
The problem occurs since the Generic AP tasks I/O limiter implementation acts on update-confirmation while the Profinet implementation check runs on update request.
It is expected that Generic AP task can run in Free Run I/O Mode without an issue.
Attachments
Issue Links
- relates to
-
PSPNSV5-42 Fatal error when host handshakes I/O areas fast
- Closed
- requested
-
PSPNSV5-53 Upgrade Profinet Core to V1.8.0.1
- Closed