Details
-
Type: Bug
-
Status: Closed
-
Priority: Minor
-
Resolution: Fixed
-
Affects Version/s: V1.2.0.0, V1.3.0.0
-
Fix Version/s: V1.4.1.0
-
Component/s: None
-
Labels:None
-
Sprint:PI Sprint 2016 KW 47/48
-
Account:SPC Profinet Core (SPCPROFINET)
Description
The current implementation regards an IOxS as valid if its value is exactly 0x80. According to specification only the DataStatus bit (mask 0x80) shall be considered for this purpose. Other bits shall be ignored at the receiver side.