Uploaded image for project: 'OpenModbus TCP V5'
  1. OpenModbus TCP V5
  2. PSOMBV5-267

In IO-Mode with Register Windows an FC23 request crossing the IO image boundary fails with an unexpected error.

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: None
    • Fix Version/s: V5.3.0.2
    • Labels:
    • Account:
      SPC Open Modbus TCP (SPCOPENMODTCP)

      Description

      In IO-Mode with Register Windows an FC23 request crossing the IO image boundary fails with an Exception Code 11 (Gateway Target Device Failed to Respond) instead of "Illegal data address" (2).

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  Alexander.Ivanov Alexander Ivanov
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: