Details
-
Type: Change
-
Status: Closed
-
Priority: Minor
-
Resolution: Fixed
-
Affects Version/s: None
-
Component/s: None
-
Labels:None
-
Sprint:VARNA KW36 / 37, VARNA KW38 / 39, VARNA KW42 / 43
-
Account:SPC Open Modbus TCP (SPCOPENMODTCP)
-
Epic Link:
Description
To fulfill the requirement of the specification MODBUS Messaging on TCP/IP Implementation Guide V1.0b Modbus-IDA (October 24, 2006) there should be no limit in the usable Unit identifier
Excerpt from the specification:
When addressing a MODBUS server connected directly to a TCP/IP network, it’s recommended not using a significant MODBUS slave address in the “Unit Identifier” field. In the event of a re-allocation of the IP addresses within an automated system and if a IP address previously assigned to a MODBUS server is then assigned to a gateway, using a significant slave address may cause trouble because of a bad routing by the gateway. Using a non-significant slave address, the gateway will simply discard the MODBUS PDU with no trouble. 0xFF is recommended for the “Unit Identifier" as non-significant value.
Remark : The value 0 is also accepted to communicate directly to a MODBUS/TCP device.